| Measuring Parameter | Monitors Over Load (As per NEMA Curve), Over Current, Under Current / Dry run, Locked current, Over voltage, Under Voltage, Phase failure | 
| Electrical Connection | 1Ø - 2 | 
| Test / Reset | Manual / Auto reset | 
| LED Indication | Power ON, Current and Voltage parameter | 
| Voltage Measuring Range | 180 to 300V AC (L - N) | 
| Power Consumption | 40VA (max) | 
| Motor Rated Current Measuring | 1A to 30A | 
| Output Contact | Control Output 1 NO Relay,  Relay Rating 30A@277V AC  | 
  
| 
       Accuracy  | 
    Current Accuracy ±5% of rated current,  Voltage Accuracy ±1% of 300V, Time Accuracy ±5% ±100msec  | 
  
| 
       Functional Specifications  | 
    Over Load NEMA class 5, 10, 15, 20, 30,  Over Current Ranges 10% - 70% of Ir (Rated Current), Under Current 20% - 80% of Ir (Rated Current), Locked Current / Stall Current Fixed : 300% of Ir (Rated Current), Over Voltage Fixed (280V), Under Voltage Fixed (180V), Phase Loss Yes (<160V)  | 
  
| 
       Time Setting  | 
    Power ON Delay 1sec (Fixed)Trip Time Delay 0, 2, 4, 6, 8 & 10 sec,  (Current & Voltage parameters), Auto Reser Time 15min, (Current & Voltage parameters), Phase Loss Trip Time Instantaneous (<120ms)  | 
  
| Auto Restart Attempts | 3 (Fixed) | 
| Mounting | DIN Rail Mount | 
| Size | DIN 66.50 x 70 x 90 (H x W x L) |