Measuring Parameter | Monitors Dry/Under Current, Over Current, Locked Current, Over Voltage, Under Voltage, Phase Failure and Overload |
Electrical Connection | 1Ø - 2 |
Test / Reset | Manual / Auto reset |
LED Indication | Power ON, Trip indication |
Display | Power 3 Digits, 7 Segment LED display |
Voltage Measuring Range | 180 to 300V AC (L - N) |
Power Consumption | 180 40VA (max) |
Motor Rated Current Measuring range | 1A to 30A |
Output Contact | Control Output 1 NO Relay, Relay Rating 32A@277V AC |
Accuracy |
Current Accuracy ±5% of rated current, Voltage Accuracy ±1% of 300V, Time Accuracy ±5% ±100msec |
Functional Specifications |
Over load NEMA class 5, 10, 15, 20, 30, Over current ranges [Ir (Rated current) + 1 to 32A], Under current [0.2A to Ir (Rated current) - 1], Locked current / Stall current [Ir (Rated current) + 1 to 32A], Over voltage 180V - 300V AC ( L - N ), Under voltage 180V - 300V AC ( L - N ) |
Time Setting |
Power ON delay 1sec (Fixed), Trip time delay (Current & Voltage parameters) 0 - 999sec Recovery time (Current & Voltage parameters) 1 - 999sec, Reset attempts 3 (fixed), Reset Attempt Time Frame 1 - 999 mins |
Auto Restart Attempts | 3 (Fixed) |
Mounting | DIN Rail Mount |
Size | 66.50 x 70 x 90 (H x W x L) |