Input Voltage |
90 - 264 VAC (127 - 370 VDC) |
Input Frequency |
50/60 Hz |
Inrush Current |
< 48 Amps; Measured at 264 VAC, 25°C Ambient, Cold start |
Output Voltage |
12V to 48V |
Output Power |
120 W |
Voltage Tolerance |
± 1 % |
Line Regulation |
< 1% of Vout |
Load Regulation |
± 1 % |
Turn On Time |
< 1 sec @ 230 VAC & < 3 sec @ 115 VAC, Full load |
Hold Up Time |
≥60ms at 230V AC & ≥15ms at 115V AC, Full load |
Rise Time |
< 100 ms |
Overload Protection |
> 110% of rated output current; Hiccup type; Autorecovery |
Overvoltage Protection |
Latched type; Input AC power to be recycled to recover the power supply |
Output Short Circuit Protection |
Hiccup mode when output is shorted; Autorecovery type |
Operating Temperature |
- 25°C to + 70°C; De-rate linearly above 50°C from 100 % load at 50°C to 50 % load at 70°C,- 25°C to 0°C start-up is guaranteed with specification deviation |
Storage Temperature |
- 40°C to + 85°C |
Cooling |
Natural convection cooled |
Humidity |
5 to 95 % RH, Non condensing |
Altitude |
2000 m |
Dimension |
43 x 109.8 x 102.7 mm (W x H x D) |
Weight |
350 gms |
Mounting |
35 mm Din rail |