Input Voltage |
90 - 264 VAC (127 - 370 VDC) |
Input Frequency |
50/60 Hz |
Inrush Current |
< 60 Amps; Measured at 264 VAC, 25°C Ambient, Cold start |
Output Voltage |
12 V to 48 V< |
Output Power |
40 W |
Voltage Tolerance |
± 1 % |
Line Regulation |
± 1 % |
Load Regulation |
± 1 % |
Turn On Time |
< 1 sec @ 230 VAC & < 3 sec @ 115 VAC, Full load |
Hold Up Time |
≥ 25 ms @ 230 VAC & ≥ 6 ms @ 115 VAC, Full load |
Rise Time |
< 100 ms |
Overload Protection |
> 110 % of rated output current; Hiccup mode; Autorecovery type |
Overtemperature Protection |
Power supply shuts down when the temperature of PCB below main transformer reaches typically 120°C;
Turns on only after the temperature falls below 90°C typically and AC power is recycled thereafter |
Overvoltage Protection |
Hiccup mode when output over voltage occur; Autorecovery type |
Output Short Circuit Protection |
Hiccup mode when output is shorted; Autorecovery type |
Operating Temperature |
- 25°C to + 70°C; De-rate linearly above 50°C from 100 % load at 50°C to 50 % load at 70°C.
-25°C to 0°C startup is guaranteed with specification deviation(Output ripple can be more than 10 % of the output voltage.) |
Storage Temperature |
- 40°C to + 85°C |
Cooling |
Natural convection cooled |
Humidity |
5 to 95 % RH, Non condensing |
Altitude |
2000 m |
Dimension |
35 x 90 x 60 mm ( W x H x D ) |
Weight |
< 150 gms |
< 150 gms |
35 mm DIN Rail |