| Rating | 7.5kVA |
| Nominal input voltage | 400V AC |
| Normal operating voltage range | 320 – 480V AC for ±1% full regulation |
| Max rated input current | 14A per phase |
| Input MCB rating | 20A |
| Relaxed operating voltage range | 277 – 520V AC for ±10% compensation |
| Selectable output voltage | 380V/ 400V/ 415V |
| Max rated output current | 11A per phase |
| Power Efficiency | Typically over 97% (with 20-100% load conditions) |
| Communication interface | MODBUS RS485 protocol |
| Power Consumption | 100VA per phase |
| Protections | IP20, Line overcurrent, over voltage, under voltage |